Loop Burnout Alarm
Initial Setting Level
alt1
12
Operation Level
PV/SP
C
25.0
100.0
PID Setting Level
Display PID
d.pid
Selection
2
PID 2 LBA
2.lba
Detection Time
0
2.lba
10
Initial Setting Level
Input Type
in-t
5
Move to Ad-
amov
vanced Function
Setting Level
0
Advanced Function Setting Level
Parameter
init
Initialization
off
Advanced Function Setting Level
LBA Level
C
lbal
8.0
C
lbal
8.0
Advanced Function Setting Level
LBA Band
C
lbab
3.0
C
lbab
3.0
3. Press the U Key to set the parameter to 12.
To return to the operation level, press the O Key for at least one second.
4. Press the O Key to move from the operation level to the PID setting level.
5. The current PID set number will be displayed. Press the U or D Key to
select PID set 2.
6. Press the M Key to select the PID 2 LBA Detection Time parameter.
7. Press the U Key to set the parameter to 10.
8. Press the O Key for at least three seconds to move to the initial setting
level.
9. Select the Move to Advanced Function Setting Level parameter by press-
ing the M Key. (For details on moving between levels, refer to 4-8 Moving
to the Advanced Function Setting Level.)
10. Press the D Key to enter the password (−169), and move from the initial
setting level to the advanced function setting level.
11. Select the LBA Level parameter by pressing the M Key.
12. Press the U Key to set the parameter to 8.0. (The default is 8.0.)
13. Select the LBA Band parameter by pressing the M Key.
14. Press the U or D Key to set the parameter to 3.0. (The default is 3.0.)
Section 4-12
117