Advanced Function Setting Level
svst
SV Status Display Function
Function
Monitor
See
See
d.ref
Display Refresh Period
Function
Monitor
• The SP, Blank, or Manual MV in the No. 2 display for the PV/SP, PV, or
PV/Manual MV (Valve Opening) Screen is alternately displayed in 0.5-s
cycles with the control and alarm status specified for the SV status display
function.
off: No SV status display
manu: MANU is alternately displayed during manual control.
stop: STOP is alternately displayed while operation is stopped.
alm1: ALM1 is alternately displayed during Alarm 1 status.
alm2: ALM2 is alternately displayed during Alarm 2 status.
alm3: ALM3 is alternately displayed during Alarm 3 status.
alm: ALM is alternately displayed when Alarm 1, 2, or 3 is set to ON.
ha: HA is alternately displayed when a heater burnout alarm, HS
alarm, or heater overcurrent alarm is ON.
■ Related Parameters
Process value/set point, PV (operation level): Page 177
PV/MV (manual MV) (manual control level): Page 221
• This parameter delays the display refresh period for monitor values. Only
display refreshing is delayed, and the refresh period for process values
used in control is not changed.
• This function is disabled by setting the parameter to OFF.
Setting range
OFF, 0.25, 0.5, 1.0
Monitor range
Unit
Second
Section 5-10
Default
off
Default
0.25
277