Omron E5AN-H User Manual page 269

Digital controllers
Hide thumbs Also See for E5AN-H:
Table of Contents

Advertisement

Advanced Function Setting Level
See
See
at-g
AT Calculated Gain
at-h
AT Hysteresis
lcma
Limit Cycle MV Amplitude
Function
Setting
Note
See
See
248
■ Related Parameters
PID ON/OFF: Page 228, ST: Page 228 (initial setting level)
• Normally use the default values for these parameters.
• The AT Calculated Gain parameter sets the gain for when PID values are
calculated using AT. When emphasizing response, decrease the set
value. When emphasizing stability, increase the set value.
• The AT Hysteresis parameter sets the hysteresis for limit cycle operation
during autotuning when switching ON and OFF.
• The Limit Cycle MV Amplitude parameter sets the MV amplitude for limit
cycle operation during autotuning.
Parameter name
AT Calculated Gain
AT Hysteresis
Limit Cycle MV
Amplitude (See note
2.)
(1) When the temperature unit is °F, the default is 1.4.
(2) With standard models, this is displayed during standard control. With po-
sition-proportional models, this is displayed during close control (when
there is a potentiometer input).
■ Related Parameters
AT execute/cancel (adjustment level): Page 192
Control must be set to 2-PID control.
Setting range
Unit
0.1 to 10.0
---
°C or °F
Temperature
input: 0.1 to
3,240.0
Analog input:
%FS
0.01 to 9.99
5.0 to 50.0
%
Section 5-10
Default
1.0
0.8 (See note 1.)
0.20
20.0

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5cn-hE5en-h

Table of Contents