Adjustment Level
db
Position Proportional Dead Band
Function
Setting
See
See
oc-h
Open/Close Hysteresis
Function
Setting
See
See
sqrp
Extraction of Square Root Low-cut Point
Function
• This parameter sets the output hold interval (the ON/OFF switching inter-
val between the open and close outputs) for position-proportional control.
Setting range
Position proportional (close):
0.1 to 10.0
Position proportional (floating):
0.1 to 10.0
■ Related Parameters
Open/close hysteresis (adjustment level): Page 207
• This parameter provides hysteresis in position-proportional control when
the open and close outputs are switched ON or OFF.
Setting range
0.1 to 20.0
■ Related Parameters
Position proportional dead band (adjustment level): Page 207
• This parameter sets the extraction of square root low-cut point used for
the inputs. The data after extracting the square root is shown below.
Position-proportional control must be
supported.
Unit
Default
%
4.0
%
2.0
Position-proportional control must be
supported.
Unit
Default
%
0.8
The input type must be an analog
input, and the Extraction of Square
Root Enable parameter must be set
to ON.
Section 5-4
207