Moving To The Advanced Function Setting Level - Omron E5AN-H User Manual

Digital controllers
Hide thumbs Also See for E5AN-H:
Table of Contents

Advertisement

Moving to the Advanced Function Setting Level

Alarms during SP
Ramp Operation
4-8

Moving to the Advanced Function Setting Level

1,2,3...
Protect Level
Operation/Adjust-
oapt
ment Protect
0
Initial Setting/
icpt
Communica-
tions Protect
0
icpt
0
104
The operation of alarms during SP ramp operation depends on whether
alarms are set to be based on the ramp set point or the target set point (refer
to the following diagrams). The set point to be used is set in the Alarm SP
Selection parameter.
Alarm SP Selection = Ramp SP (Alarm Type: 1 (Upper/Lower Limits))
Temperature
Alarm SP Selection = Target SP (Alarm Type: 1 (Upper/Lower Limits))
Temperature
Use the following procedure to move to the advanced function setting level.
1. Press the O and M Keys simultaneously for at least three seconds in op-
eration level.
Note The key pressing time can be changed in the Move to Protect Level
Time parameter (advanced function setting level).
2. The Controller moves to the protect level, and the Operation/Adjustment
Protect parameter is displayed.
3. Press the M Key once to move to the Initial Setting/Communications Pro-
tect parameter.
4. Set the set value to 0. The default setting is 0 (possible to reach).
Alarm output ON
Alarm output ON
Time
Alarm output ON
Alarm output ON
Time
Section 4-8

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5cn-hE5en-h

Table of Contents