Settings: Heater Short Alarm - Omron E5AN-H User Manual

Digital controllers
Hide thumbs Also See for E5AN-H:
Table of Contents

Advertisement

Using Heater Burnout, Heater Short, and Heater Overcurrent Alarms
hb1
2.5

3-10-6 Settings: Heater Short Alarm

Operating Procedure
Operation Level
PV/SP
C
25.0
100.0
Initial Setting Level
Input Type
in-t
5
Initial Setting Level
amov
-169
Advanced Function Setting Level
Move to the
init
Advanced
Function
off
Setting Level
HS Alarm
hsu
Use
on
9. For this example, set 2.5. To return to the operation level, press the O
Key for less than one second.
To activate the HS alarm, set the HS Alarm Use parameter to ON in the
advanced function setting level and set the HS Alarm 1 and HS Alarm 2
parameters in the adjustment level.
This procedure sets the HS Alarm 1 parameter to 2.5.
Moving to the Advanced Function Setting Level
The HS Alarm Use parameter setting is already ON by default, so set the HS
Alarm 1 parameter.
1. Move to the advanced function setting level.
Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
2. Select Move to Advanced Function Setting Level by pressing the M Key.
(For details on moving between levels, refer to 4-8 Moving to the Ad-
vanced Function Setting Level.)
3. Press the D Key to enter the password (−169), and move from the initial
setting level to the advanced function setting level.
The top parameter in the advanced function setting level is displayed.
4. Select the HS Alarm Use parameter by pressing the M Key.
Check that this parameter is set to ON (the default).
Next, set the HS Alarm 1 parameter.
Section 3-10
79

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5cn-hE5en-h

Table of Contents