Omron E5AN-H User Manual page 341

Digital controllers
Hide thumbs Also See for E5AN-H:
Table of Contents

Advertisement

Parameters
Characters
alt1
Alarm 1Type
alh1
Alarm 1 Hysteresis
alt2
Alarm 2 Type
alh2
Alarm 2 Hysteresis
alt3
Alarm 3 Type
alh3
Alarm 3 Hysteresis
Transfer Output Type tr-t
tr-h
Transfer Output
Upper Limit
320
Setting (monitor) value
0: Alarm function OFF
1: Upper and lower-limit
alarm
2: Upper-limit alarm
3: Lower-limit alarm
4: Upper and lower-limit
range alarm
5: Upper and lower-limit
alarm with standby
sequence
6: Upper-limit alarm with
standby sequence
7: Lower-limit alarm with
standby sequence
8: Absolute-value upper-limit
alarm
9: Absolute-value lower-limit
alarm
10: Absolute-value upper-limit
alarm with standby
sequence
11: Absolute-value lower-limit
alarm with standby
sequence
12: LBA (Loop Burnout Alarm)
13: PV change rate alarm
14: Remote SP absolute
value upper limit alarm
(See note 1.)
15: Remote SP absolute
value lower limit alarm
(See note 1.)
Temperature input: 0.1 to
3240.0
Analog input: 0.01 to 99.99
Same settings as the alarm 1
type.
Note The 12: LBA (Loop
Burnout Alarm) setting
cannot be used.
Temperature input: 0.1 to
3240.0
Analog input: 0.01 to 99.99
Same settings as the alarm 2
type
Temperature input: 0.1 to
3240.0
Analog input: 0.01 to 99.99
OFF: OFF
SP:
Set point (See note 2.)
SP-M: Ramp set point
PV:
Process value
MV:
Manipulated variable
(heating) (See note 3.)
C-MV: Manipulated variable
(cooling) (See note 4.)
V-M:
Valve Opening (See
note 5.)
See note 6.
Display
Default
2
0.2
0.02
2
0.2
0.02
2
0.2
0.02
off
OFF
sp
sp-m
pv
mv
c-mv
v-m
See note 6. See note 6.
Appendix
Unit
Set value
None
°C or °F
%FS
None
°C or °F
%FS
None
°C or °F
%FS
None