Omron E5AN-H User Manual page 321

Digital controllers
Hide thumbs Also See for E5AN-H:
Table of Contents

Advertisement

Rating and Characteristics of Options
Event inputs
Contact Input
ON: 1 kΩ max., OFF: 100 kΩ min.
Non-contact Input
ON: Residual voltage 1.5 V max.; OFF: Leakage current 0.1 mA max.
Communications
Transmission path: RS-485/232C/RS-422
Communications method: RS-485 (2-wire, half duplex), RS-232C or RS-422 (4-wire, half duplex)
Synchronization: Start-stop
Baud rate: 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, or 57.6 kbps
4 to 20 mA DC, Load: 600 Ω max., Resolution: Approx. 10,000, Accuracy: ±0.3%
Transfer output
Current Transformer (CT)
Specifications
Item
Model number
Max. continuous current
Dielectric strength
Vibration resistance
Weight
Accessories
Note The maximum continuous current of the E5@N-H is 50 A.
External Dimensions
E54-CT1
300
Specifications
E54-CT1
50 A
1,000 VAC (for 1 min)
2
50 Hz, 98 m/s
Approx. 11.5 g
None
2.8
21
15
40
30
E54-CT3
120 A (See note.)
Approx. 50 g
Armature (2), Plug (2)
Appendix