Combining A Simple Program With An Sp Ramp - Omron E5AN-H User Manual

Digital controllers
Hide thumbs Also See for E5AN-H:
Table of Contents

Advertisement

Using the Simple Program Function

4-16-3 Combining a Simple Program with an SP Ramp

The program END status can also be cleared using an event. If the program
start function is assigned to an event, however, the program end status cannot
be cleared from the Program Start parameter display, which will function only
as a monitor display.
Control can be combined with the SP ramp by setting the SP Ramp Set Value
and Soak Time parameters for each bank.
SPn
Ramp SP
SPn-1
PV
Bank n
If the program moves to the next bank at the end of the soak time before the
ramp SP reaches the SP, the SP ramp operation will extend across the banks
as shown below as long as the SP Ramp Set Value parameter is not set to 0.
SPn
Ramp SP
SPn-1
PV
Bank n
If the SP Ramp Set Value parameter is set to 0 for the next bank, SP ramp
operation will be stopped as shown below.
SPn
SPn-1
Ramp SP
PV
Bank n
Wait band
Wait band
SPn+1
Soak time
SPn+1
Soak time
SPn+1
Soak time
Section 4-16
Wait band
Wait band
Bank n+1
Bank n+1
Bank n+1
137