Advanced Function Setting Level
Mode
Linked to
PV stable
band
See
See
pv-b
PV Stable Band
Function
Setting
Note
See
See
254
Setting
Function
Low
r-g.r
Red to
Red
Green to
Red
g-o.r
Green to
Green
Orange to
Red
o-g.r
Orange to
Orange Green
Green to
Red
■ Related Parameters
PV stable band (advanced function setting level): Page 254
This parameter sets the PV stable band width within which the PV display
color is changed.
• When the mode to link to the PV stable band is selected with the PV
Change Color parameter, the PV display color will change according to
whether the present value (PV) is lower than, within, or higher than the PV
stable band, as shown in the following figure.
• There is a hysteresis of 0.2 (°C or °F).
PV stable
band
Low
0.2 (°C or °F)
Models
Controllers with Thermocouple/Resis-
tance Thermometer Universal Inputs
Controllers with Analog Inputs
Set "None" as the unit for Controllers with Analog Inputs.
■ Related Parameters
PV change color (advanced function setting level): Page 253
PV change color
Within
Within
PV stable
PV stable
band
band
Low
Within
SP
PV stable band
High
Green
Red
Orange
Red
Red
PV stable
band
Within
High
SP
0.2 (°C or °F)
When analog inputs are used: 0.02 (%FS)
Setting range
0.1 to 999.9
0.01 to 99.99
Section 5-10
Application example
High
PV
Application example
To display stable status
To display stable status
To display stable status
PV
Unit
Default
°C or °F
5.0
(See note.)
%FS
5.00