Omron E5AN-H User Manual page 144

Digital controllers
Hide thumbs Also See for E5AN-H:
Table of Contents

Advertisement

Performing Manual Control
amad
on
Initial Setting Level
Input Type
in-t
5
Operation Level
Auto/Manual
a-m
Switch
Manual Control Level
PV/MV
C
25.0
0.0
C
25.0
50.0
Operation Level
C
25.0
alm
100.0
Operating Procedure
Operation Level
C
25.0
alm
100.0
Initial Setting Level
Input Type
in-t
5
cntl
pid
Initial Setting Level
Move to Ad-
amov
vanced Function
Setting Level
0
6. Use the U Key to set the parameter to ON. (The default is ON.)
7. Press the O Key for at least one second to move from the advanced
function setting level to the initial setting level.
8. Press the O Key for at least one second to move from the initial setting
level to the operation level.
9. Select the Auto/Manual Switch parameter by pressing the M Key.
10. Press the O Key for at least three seconds to move from the operation
level to the manual control level.
11. Press the U or D Key to set the manual MV. (In this example, the MV is
set to 500%.)
Note
The manual MV setting must be saved (see page 14), but values
changed with Key operations are reflected in the control output
immediately.
12. Press the O Key for at least one second to move from the manual control
level to the operation level.
In this example, A-M (Auto/Manual) is set for the PF Setting parameter
(E5AN/EN-H only).
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
2. Select the PID ON/OFF parameter by pressing the U Key. (The default
is PID.)
3. Select the Move to Advanced Function Setting Level parameter by press-
ing the M Key. (For details on moving between levels, refer to 4-8 Moving
to the Advanced Function Setting Level.)
Section 4-13
123

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5cn-hE5en-h

Table of Contents