Platinum Resistance Thermometer Calibration (Thermocouple/Resistance Thermometer Input)

6-4
Platinum Resistance Thermometer Calibration
(Thermocouple/Resistance Thermometer Input)
adj
30
Input type 0:
p390
e20c
Input types 1, 2, 3, 4, 24:
p280
e26b
Input type 0:
p200
93a7
Input types 1, 2, 3, 4, 24:
p140
e26b
In this example, calibration is shown for Controller with a resistance thermom-
eter set as the input type.
Use connecting wires of the same thickness.
1,2,3... 1. Connect the power supply.
2. Connect a precision resistance box (called a "6-dial" in this manual) to the
platinum resistance thermometer input terminals, as shown in the follow-
ing diagram.
Input power supply
Input power supply
3. Turn the power ON.
4. Move to the calibration level.
This starts the 30-minute aging timer. This timer provides an approximate
timer for aging. After 30 minutes have elapsed, the No. 2 display changes
to 0. You can advance to the next step in this procedure even if 0 is not
displayed.
5. Execute calibration for the main input.
Press the M Key to display the count value for each input type.
The No. 2 display at this time shows the currently entered count value in
hexadecimal. Set the 6-dial as follows:
• Input type 0:
• Input type 1, 2, 3, 4 or 24: 280 Ω
Allow the count value on the No. 2 display to fully stabilize, then press the
D Key to temporarily register the calibration settings.
If this count value is outside of the specified range, the No. 2 display will
flash and the count value will not be temporarily registered.
Press the M Key to display the count value for each input type.
The No. 2 display at this time shows the currently entered count value in
hexadecimal. Set the 6-dial as follows:
• Input type 0: 200 Ω
• Input type 1, 2, 3, 4 or 24: 140 Ω
Allow the count value on the No. 2 display to fully stabilize, then press the
D Key to temporarily register the calibration settings.
If this count value is outside of the specified range, the No. 2 display will
flash and the count value will not be temporarily registered.
E5CN-H
9
10
A
3
B'
4
B
5
E5AN/EN-H
1
2
A
18
B'
19
B
20
390 Ω
Section 6-4
6-dial
6-dial
289