Using the Simple Program Function
Program Pattern
Any of three program patterns can be selected. The simple program will not
be run if the Program Pattern parameter is set to OFF.
Program Pattern
OFF
STOP
CONT
LOOP
• Banks where the Soak Time parameter is set to 0 will not be executed.
• The bank number can be changed even during program operation by using either an
event input or key operations.
• The bank number is initialized to 0 when the program pattern is changed.
■ Pattern 1 (STOP)
Control will stop and the STOP mode will be entered when the program has
ended.
SP
Set point n
PV
Operation
Program will not be executed.
• Program operation will start when the Program Start parame-
ter is changed from RSET to STRT. The bank number will be
automatically incremented by one when the Soak Time
parameter setting for the bank has elapsed.
• After the bank specified in the Valid Program Bank parame-
ter has been executed, program operation will be ended. The
RUN/STOP status will become STOP, and the program end
output will be turned ON.
• Program operation will start when the Program Start parame-
ter is changed from RSET to STRT. The bank number will be
automatically incremented by one when the Soak Time
parameter setting for the bank has elapsed.
• After the bank specified in the Valid Program Bank parame-
ter has been executed, program operation will be ended. The
RUN/STOP status will continue as RUN (control will continue
at the SP at the end bank), and the program end output will
be turned ON.
• Program operation will start when the Program Start parame-
ter is changed from RSET to STRT. The bank number will be
automatically incremented by one when the Soak Time
parameter setting for the bank has elapsed.
• After the bank specified in the Valid Program Bank parame-
ter has been executed, the bank number will return to 0 and
the program execution will continue.
Soak time
Automatically switches from RUN to STOP mode.
Bank n (end bank)
Section 4-16
Wait band
Wait band
END display
END output