Omron E5AN-H User Manual page 36

Digital controllers
Hide thumbs Also See for E5AN-H:
Table of Contents

Advertisement

Communications Function
Note
Setting Communications
Data
Parameter name
Symbol
psel
Protocol Setting
u-no
Communications
Unit No.
bps
Communications
Baud Rate
len
Communications
Data Length
sbit
Communications
Stop Bits
prty
Communications
Parity
sdwe
Send Data Wait
Time
2. Press the O Key for less than one second to move from the initial setting
level to the communications setting level.
3. Select the parameters as shown below by pressing the M Key.
4. Press the U or D Key to change the parameter setting.
Protocol Setting
psel
cwf
M
u-no
Communications Unit No.
1
M
Communications Baud Rate
bps
9.6
M
Communications Data Length
len
(See note.)
7
M
sbit
Communications Stop Bits
(See note.)
2
M
prty
Communications Parity
even
M
Send Data Wait Time
sdwt
20
M
The Protocol Setting parameter is displayed only when CompoWay/F commu-
nications are being used.
Match the communications specifications of the E5CN/AN/EN-H and the host
computer. If a 1:N connection is being used, ensure that the communications
specifications for all devices in the system (except the communications Unit
No.) are the same.
Setting (monitor) value
CompoWay/F (SYSWAY),
Modbus
0 to 99
1.2, 2.4, 4.8, 9.6, 19.2,
38.4, 57.6
7, 8
1, 2
None, Even, Odd
0 to 99
Selection symbols
cwf, mod
1.2, 2.4, 4.8, 9.6, 19.2, 38.4.
57.6
none, even, odd
Section 1-4
Default
Unit
CompoWay/F
None
(SYSWAY)
1
None
9.6
kbps
7
Bits
2
Bits
Even
None
20
ms
15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5cn-hE5en-h

Table of Contents