Initial Setting Examples
Example 3
Input type:
Control method:
SP ramp time unit: EU/min (default)
Travel time:
SP ramp set value: 10.0 EU (°C)
Set point:
Setup Procedure
Initial Setting
Level
Adjustment
Level
48
5 (K thermocouple,
−200.0°C to 1,300.0°C)
Floating control (default)
45 s
250°C
Power ON
Set input
specifications
Set control
specifications
Set travel time
Set SP ramp
Start operation
Power ON
Operation Level
25.0
c
PV/SP
0.0
Press the O key for
at least 3 s.
Control stops.
Initial Setting
Level
in-t
Check input type.
Input Type:
5
M
Floating
Check that control
clfl
control:
method is floating
flot
Close control:
control.
M
mot
Use the U and D
keys to set the
Travel time:
45
travel time to 45.
M
Press the O key for
at least 1 s.
Control starts.
Operation Level
25.0
Use the U and
c
PV/SP:
D keys to set the
250.0
250.0
SP to 250.0°C.
Press the O key
(for less than 1 s).
Adjustment
Level
at
off
M
sprt
Use the U and D
SP ramp set value:
keys to set the SP
10.0
10.0
ramp set value to
10.0°C.
Press the O key
(for less than 1 s).
Operation Level
25.0
c
PV/SP:
250.0
250.0
M
r-5
Running
Confirm that
control is running.
run
Stopped
M
Start operation.
Section 3-1
5
flot
clos
45
run
stop