Initial Setting Level
tr-t
Transfer Output Type
Setting
See
See
• This parameter sets the transfer output type.
• The following table shows the differences between models with a transfer
output and models without a transfer output that use control output 1 or
control output 2 as a simple transfer output.
Transfer Output Destination
Transfer
Control output 1
output
Yes
---
No
Current output or
linear voltage out-
put
No
Current output or
linear voltage out-
put
No
Relay output, volt-
age output (for
driving SSR), or
SSR output
No
Relay output, volt-
age output (for
driving SSR), or
SSR output
■ Precision and User Calibration
Transfer output
Simple transfer output Not specified.
Note For details on the calibration method, refer to SECTION 6 CALI-
BRATION.
Transfer output type
OFF
Set point
Set point during SP ramp
PV
MV monitor (heating)
MV monitor (cooling)
Valve opening
]
■ Related Parameter
Transfer output upper limit, Transfer output lower limit (initial setting level):
Page 236
There must be a transfer output, cur-
rent output, or linear voltage output.
Control output 2
---
No
Relay output, voltage
output (for driving SSR),
or SSR output
Current output or linear
voltage output
Current output or linear
voltage output
No
Relay output, voltage
output (for driving SSR),
or SSR output
Precision
±0.3% FS
off
off
sp
sp-m
pv
mv
c-mv
v-m
Section 5-9
Transfer output
destination
Transfer output
Control output 1
Control output 1
Control output 2
No
User calibration
Supported. (See note.)
Not supported.
Default
235