Displaying PV/SV Status
Operating Procedure
Initial Setting Level
Input Type
in-t
5
Initial Setting Level
Move to Ad-
amov
vanced Function
Setting Level
-169
Advanced Function Setting Level
Parameter
init
Initialization
off
PV Status
pvst
Display
Function
off
PV Status
pvst
Display
Function
alm1
Initial Setting Level
Input Type
in-t
5
Operation Level
C
25.0
alm1
100.0
154
(1) Alternating display in SV status display
(2) Alternating display during program end output
(3) Flashing display during auto-tuning
(4) Alternating display when a control output ON/OFF count alarm occurs
(5) Flashing display when out of the setting range
This procedure sets the PV Status Display Function parameter to ALM1.
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
2. Select the Move to Advanced Function Setting Level parameter by press-
ing the M Key.
3. Use the D Key to enter the password (−169). It is possible to move to the
advanced function setting level by either pressing the M Key or waiting
two seconds without pressing any key.
4. Press the M Key to select the PV Status Display Function parameter.
5. Press the U Key to select ALM1.
6. Press the O Key for at least one second to move to the initial setting lev-
el.
7. Press the O Key for at least one second to move to the operation level.
If the Alarm 1 status is ON, PV and ALM1 will be alternately displayed.
Section 4-22