Table 10. System x3690 X5 IMM error messages (continued)
v Follow the suggested actions in the order in which they are listed in the Action column until the problem is solved.
v See Chapter 4, "Parts listing, System x3690 X5 Types 7147, 7148, 7149, and 7192," on page 249 to determine which components
are customer replaceable units (CRU) and which components are field replaceable units (FRU).
v If an action step is preceded by "(Trained service technician only)," that step must be performed only by a trained service
technician.
Event ID
Message
80070208-0a01xxxx
Sensor PS n Therm Fault has
80070208-0a02xxxx
transitioned to critical from a less
80070208-0a03xxxx
severe state.(n = power supply
80070208-0a04xxxx
number)
8007020f-2582xxxx
Sensor I/O Resources has transitioned
to critical from a less severe state.
Severity
Description
Error
A sensor has
changed to Critical
state from a less
severe state.
Error
I/O space
limitation.
Action
1. Make sure that there are
no obstructions, such as
bundled cables, to the
airflow from the
power-supply fan.
2. Replace power supply
n.
(n = power supply number)
1. Update the firmware
(UEFI and IMM) to the
latest level (see
"Updating the
firmware" on page 397).
2. Reseat the memory
DIMMs (see "Removing
a memory module" on
page 295 and
"Replacing a memory
module" on page 296).
3. Reseat any PCIe
adapters that are
installed (see
"Removing an adapter"
on page 274 and
"Replacing an adapter"
on page 275).
4. (Trained service
technician only) Replace
the system board (see
"Removing the system
board" on page 360 and
"Replacing the system
board" on page 363 ).
175
Chapter 3. Diagnostics