Table 10. System x3690 X5 IMM error messages (continued)
v Follow the suggested actions in the order in which they are listed in the Action column until the problem is solved.
v See Chapter 4, "Parts listing, System x3690 X5 Types 7147, 7148, 7149, and 7192," on page 249 to determine which components
are customer replaceable units (CRU) and which components are field replaceable units (FRU).
v If an action step is preceded by "(Trained service technician only)," that step must be performed only by a trained service
technician.
Event ID
Message
80010b03-1502xxxx
Numeric sensor FG 2PS going high
(upper non-recoverable) has asserted.
80010b03-1503xxxx
Numeric sensor FG 3PS going high
(upper non-recoverable) has asserted.
80010b03-1504xxxx
Numeric sensor FG 4PS going high
(upper non-recoverable) has asserted.
8003010c-2581xxxx
Sensor Lane Failover has asserted
8003010e-0701xxxx
Sensor Memory Resize has asserted
172
System x3690 X5 Types 7147, 7148, 7149, and 7192: Problem Determination and Service Guide
Severity
Description
Error
Power supply fuel
gage error.
Error
Power supply fuel
gage error.
Error
Power supply fuel
gage error.
Info
A memory lane
failover event has
occurred.
Info
A memory resize
event has occurred.
Action
1. The management
controller has detected a
sensor transitioned to
critical from less severe
on the power supply 2.
2. Make sure that the
power supply is
installed correctly (see
"Replacing a hot-swap
power supply" on page
326). Make sure that no
error LEDs are lit on the
power supply and that
all power supplies have
the green LEDs lit.
1. The management
controller has detected a
sensor transitioned to
critical from less severe
on the power supply 3.
2. Make sure that the
power supply is
installed correctly (see
"Replacing a hot-swap
power supply" on page
326). Make sure that no
error LEDs are lit on the
power supply and that
all power supplies have
the green LEDs lit.
1. The management
controller has detected a
sensor transitioned to
critical from less severe
on the power supply 4.
2. Make sure that the
power supply is
installed correctly (see
"Replacing a hot-swap
power supply" on page
326). Make sure that no
error LEDs are lit on the
power supply and that
all power supplies have
the green LEDs lit.
No action; Informational
only.
No action; Informational
only.