2.2.5 AS200 Input/Output Terminals

Analog Input
Two analog signal input channels:
Analog Signal
Resolution
Input impedance
Conversion time
Analog to digital
conversion range
Digital value
output
You can use the program to read the values in SR to obtain the corresponding A/D conversion value for the
channel.
Analog Output
Two analog signal output channels:
Analog Signal
Resolution
Impedance
allowance
Conversion time
Analog to digital
conversion range
Digital value
output
You can use the instruction MOV to move the value to the SR to obtain the corresponding voltage output
value.
Item
Item
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Voltage Input
-10 to +10 V
12-bit
1 MΩ
3 ms / CH
-2000 to 2000
SR168 (CH1)
Voltage output
-10 to +10 V
12-bit
≥1 k Ω
2ms / CH
-2000 to 2000
SR172 (CH1)
Current input
-20 to 20 mA
4 to 20mA (for FW V1.08 or later)
11-bit
250 Ω
-1000 to 1000 (-20 to 20 mA)
0 to 1000 (4 to 20mA)
SR169 (CH2)
Current output
0 to 20 mA
12-bit
≤500 Ω
0 to 4000
SR173 (CH2)