Analog Input Terminals (Avi, Aci, Aui, Acm) - Delta C2000 Series User Manual

Classical field oriented control ac motor drive
Hide thumbs Also See for C2000 Series:
Table of Contents

Advertisement

Terminals
Terminal Function
AFM1
AFM2
ACM
Analog Signal Common
STO1
Default setting is shorted
SCM1
Power removal safety function for EN954-1 and IEC/EN61508
STO2
When STO1~SCM1;STO2~SCM2 is activated, the activation current is 3.3mA 11Vdc
SCM2
SG+
SG-
Modbus RS-485
SGND
PIN 1,2,7,8 : Reserved
RJ-45
PIN 4: SG-

6-2 Analog input terminals (AVI, ACI, AUI, ACM)

Analog input signals are easily affected by external noise. Use shielded wiring and keep it as
short as possible (<20m) with proper grounding. If the noise is inductive, connecting the shield to
terminal ACM can bring improvement.
If the analog input signals are affected by noise from the AC motor drive, please connect a
capacitor and ferrite core as indicated in the following diagram.
Digital inputs (FWD, REV, MI1~MI8, COM)
When using contacts or switches to control the digital inputs, please use high quality components
to avoid contact bounce.
The "COM" terminal is the common side of the photo-coupler. Any of wiring method, the "common
point" of all photo-coupler must be the "COM".
0~10V Max. output current 2mA, Max. load 5k
-10~10V maximum output current 2mA, maximum load 5k
Output current: 2mA max
Resolution: 0~10V corresponds to Max. operation frequency
Range: 0~10V
AFM 1 Switch, factory setting is 0~10V
0~10V Max. output current 2mA, Max. load 5k
0~20mA Max. load 500
Output current: 20mA max
Resolution: 0~10V corresponds to Max. operation frequency
Range: 0~10V
AFM 2 Switch, factory setting is 0~10V
Common for analog terminals
PIN 3, 6: SGND
PIN 5: SG+
NOTE: Wire size of analog control signals: 18 AWG (0.75 mm
Wind each wires 3 times or more around the core
Chapter 6 Control Terminals C2000 Series
Factory Setting (NPN mode)
-10~+10V
4~20mA
6-5
2
) with shielded wire

Hide quick links: