Send Quote Requests to info@automatedpt.com
2. Data Exchange Parameters
Click Data Exchange tab and click the Data Exchange device. After that click Edit to open the data exchange
setting page.
Name
General Setting
I/O Parameter Setting
Item
Select the connection from the EDS file. Different connections
Connection Manager
may have different exchange parameters.
EIP Scanner checks the followings according to the setting:
EDS Compare Rule
Enable
Enable or disable the data exchange.
Use EtherNet/IP Tag to perform data exchange with adapters.
You must create a Consumed Tag in the Global Symbols in
ISPSoft before using this function. After selecting this check box,
EtherNet/IP Tag
Requested Packet
Interval (RPI)
Multicast
Timeout
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Description
Disable keying: Disable key checking the product
information and versions.
Compatible keying: Check the product information (Vendor
ID, Device Type, Product Code), and Major Revision
(should be matched). Minor revision is not checked.
Exact match: Check the product information, major
revision and minor version should be matched with what
stated in EDS file.
The directional arrow points left of () (READ only)
Registers cannot be used in this row.
The length format is defined by the data format in the
Global Symbols; you cannot change the length format
here.
Refer to section 9.4.6 for more details
Time interval to request packets through the I/O
connection, unit: ms
Click Apply to all: to apply the I/O parameter settings to
all the items on the data exchange list.
Communication mode setup: Multicast or Point-to-Point
Point-to-Point is more common; use Multicast when the
connection is Listen_only.
Sets the timeout according to the RPI or a multiple of RPI
(RPI*X).
Click Apply to all: to apply the settings to all the items on