Delta AS Series Operation Manual page 90

Hide thumbs Also See for AS Series:
Table of Contents

Advertisement

Send Quote Requests to info@automatedpt.com
*3: Logging function should be used with API instructions.
*4: Disconnecton detecton can only be used in the modes of 4 mA to 20 mA and 1V to 5 V.
Functional specifications for the analog-to-digital conversion – Voltage Input
Analog-to-Digital
Conversion
Rated Input Range
Rated Conversion
Range
Hardware Input Limit*
Conversion Limit*
*1: If the input signal exceeds the hardware input limit, the module only shows the maximum value. If the input
signal is below the lower limit, it only shows the minimum value. And an error flag will be set.
*2: If the input signal exceeds the hardware input limit, it also exceeds the conversion limit and a conversion
limit error appears. For example in the voltage input mode (-10 V to +10 V), when the input signal is 10.15 V,
exceeding the hardware upper limit, it also exceeds the conversion upper limit. The module uses the upper
limit value (32384) as the input signal and a conversion limit error appears.
Functional specifications for the analog-to-digital conversion – Current Input
Analog-to-Digital
Conversion
Rated Input Range
Rated Conversion
Range
Hardware Input Limit*
Conversion Limit*
*1: If the input signal exceeds the hardware input limit, the module only shows the maximum value. If the input
signal is below the lower limit, it only shows the minimum value. And an error flag will be set.
*2: If the input signal exceeds the hardware input limit, it also exceeds the conversion limit and a conversion
limit error appears. For example in the voltage input mode (4 mA to 20 mA), when the input signal is 0 mA,
exceeding the hardware upper limit, it also exceeds the conversion upper limit. The module uses the upper
limit value (-384) as the input signal and a conversion limit error appears.
-10V~10V
K-32000
~
K0~K32000
K32000
-
1
-0.12V~10.12V -5.06V~5.06V
10.12V~10.12V
K-32384
2
~
K-384~K32384
K32384
±20mA
K-32000
~
K32000
1
-20.24mA~20.24mA
2
K-32384~ K32384
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Voltage Input
0V~10V
±5V
K-32000
~
K32000
K-32384
~
K32384
Current Input
0mA~20mA
K0~K32000
-0.24mA~20.24mA
K-384~K32384
0V~5V
1V~5V
K0~K32000
K0~K32000
-0.06V~5.06V
0.95V~5.05V
K-384~K32384 K-384~K32384
4mA~20mA
K0~K32000
3.81mA~20.19mA
K-384~K32384

Hide quick links: