Group 3: Output Function Parameters
Multi-function Output Relay (RA1, RB1, RC1)
03 - 00
03 – 01
Multi-function Output Terminal MO1
03 - 02
Multi-function Output Terminal MO2
Multi-function Output Terminal MO3
03 - 03
Settings
Function
00
No Function
01
AC Drive Operational
02
Master Frequency Attained
03
Zero Speed
04
Over-Torque Detection
05
Baseblock (B.B.) Indication
06
Low-Voltage Indication
07
Operation Mode Indication
08
Fault Indication
09
Desired Frequency Attained 1 Active when the desired frequency (Pr.03-04) is attained.
10
PLC Program Running
11
PLC Program Step Completed Active for 0.5 sec each time the multi-step speed is attained.
Revision 10/2005, BE13, SW V4.08
Active when there is an output from the drive or RUN command is
"ON".
Active when the AC motor drive reaches the output frequency
setting.
Active when Command Frequency is lower than the Minimum
Output Frequency.
Active as long as over-torque is detected. (Refer to Pr.06-03 ~
Pr.06-05)
Active when the output of the AC motor drive is shut off during
baseblock. Base block can be forced by Multi-function input (setting
9 or 10).
Active when low voltage(Lv) is detected.
Active when operation command is controlled by external terminal.
Active when faults occur (oc, ov, oH, oL, oL1, EF, cF3, HPF, ocA,
ocd, ocn, GFF).
Active when PLC Program is running.
Chapter 5 Parameters VFD-B Series
Factory Setting: 08
Factory Setting: 01
Factory Setting: 02
Factory Setting: 20
Description
5-47