The parameters in the TCP Socket Setting are the same as the parameters in the UDP Socket Setting except that
there is no Keep Alive Timer parameter in the UDP Socket Setting. The parameters in the TCP and UDP Socket
Setting are described below.
 Remote IP: Users can set a remote IP address.
 Remote Port: Users can set a communication port used by the remote device for this TCP connection. The port
number must be within the range between 0 and 65535.
 Local Port: Users can set a communication port used by the local CPU module for this connection. The port
number must be within the range between 0 and 65535.
 Send Address: Uses can set the initial device in the CPU module where data which will be sent is stored.
 Send Length: Users can set the length of data which will be sent by the local CPU module. The length must be
within the range between 0 and 200 bytes. For PLC CPU with FW V1.06.20 or later, the range is between 0 and
512 bytes.
 Receive Address: Uses can set an initial device in the CPU module where data which will be received is stored.
 Receive Length: Users can set the length of data which will be received by the local CPU module. The length
must be within the range between 0 and 200 bytes. For PLC CPU with FW V1.06.20 or later, the range is
between 0 and 512 bytes.
 Keep Alive Timer: Users can set a maximum keep alive time for the connection. If no data is transmitted, and
the keep alive period has elapsed, the CPU module will terminate the connection automatically.
The port number used by the local CPU module and the port number used by the remote device cannot be the same,
and the devices where data which will be sent is stored cannot overlap the devices where data which will be received
is stored. If the IP address of the remote device is 192.168.1.100, the port number used by the remote device is 65500,
and the port number used by the local CPU module is 65501, the remote device and the local CPU module can transmit
data through this TCP connection.