 Manual + Flags (I/O module of CPU and Remote module): This function is available for PLC with
firmware V1.08.50 or above and you need to use ISPSoft V3.12 or above to execute this function. Selected
this option, you can control both the right-side modules of the PLC CPU and the remote modules. The
operation is the same as the operation of the option above, Manual + Flags (only I/O module of CPU
module). Refer to the explanation on Manual + Flags (only I/O module of CPU module) for more details.
Select Action when I/O Module Parameter with Manual CONFIG Different
This determines which action is taken when the actual settings are NOT the same as the parameters that you
manually set when the previous setting option is set to Manual.
 Auto update: the CPU module is automatically configured.
 Show error: the CPU module shows an error.
CPU module Stop when I/O Module No Response
This determines how the CPU module and other modules react when a connected extension module is not
responding.
 Stop: the CPU module stops running and sends an error.
 Keep Run: the CPU module and I/O modules keep running.
CPU module Stop when I/O Module Occurred Error
This determines how the CPU module reacts when a minor module error occurs.
 Stop: the CPU module stops running and sends an error.
 Keep Run: the CPU module keeps running and sends an error.
Setting delay time to detect I/O Module
This sets the timing when to start detecting the connected I/O module after CPU module is power-on.
Normally the CPU module detects its connected I/O module once it is supplied with power. But you can set the
delay time (unit: 0.1 second) for the CPU module to postpone detecting. This function is very useful when it takes
time for the supply power to be stable or when the remote I/O module is not supplied with power at the same
time as the CPU module is. With a set delay time, the detection on the connected sets can be more accurate.
Refer to the image below for the time frame.