Delta AS Series Operation Manual page 610

Hide thumbs Also See for AS Series:
Table of Contents

Advertisement

Send Quote Requests to info@automatedpt.com
Code
F3
AS01DNET enters the test mode
F4
BUS-OFF
F5
No network power
Internal error; Flash or RAM
F6
check error
Error produced in factory
F8
manufacturing
Internal error; EEPROM access
F9
failure
FA
Invalid configuration data
Identification parameters returned
E0
from the slave do not match the
configuration data.
I/O Data size returned does not
E1
match that in the scan list.
The slave device in the scan list
does not exist or is offline when
AS01DNET-A is in master mode.
E2
The I/O connection between the
slave AS01DNET-A and the
master is broken when
AS01DNET-A is in slave mode.
AS01DNET-A fails to transmit
E3
data.
Error detected in sequence of
E4
fragmented I/O data from the
slave device.
The slave device returns error
E5
when AS01DNET-A attempts to
communicate with it.
IO data size returned from the
E6
slave is bigger than that
configured in Scan List.
AS01DNET-A is checking MAC
E7
ID.
Explanation
Switch the function switch IN1 from On to Off and re-power
AS01DNET-A.
1.
2.
3.
4.
1.
2.
If the error still exists after re-power, send AS01DNET-A back for
repair.
If the error still exists after re-power, send AS01DNET-A back for
repair.
If the error still exists after re-power, send AS01DNET-A back for
repair.
1.
2.
1.
2.
3.
Re-configure I/O data size of the slave, download the configuration to
AS01DNET-A and run the PLC.
1.
2.
3.
1.
2.
Check if the slave is operating normally.
Check if the slave is operating normally.
Check that the IO data size of the slave should be the same as that
configured in Scan List.
If the code is displayed long, do the troubleshooting according to the
following steps.
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Correction
Check if the network cable is normal and the shielded cable is
grounded.
Check if the baud rates of all nodes in the network are same.
Check if the start and end of the network cable are both connected
with a 121Ω terminal resistor.
Re-power AS01DNET-A.
Check if the network cable is normal.
Ensure that the network power is normal.
Configure the network correctly and re-download it to AS01DNET-
A.
Check if the node address of one slave in the scan list is the same
as that of AS01DNET-A.
Check if there is any change in node ID of the slave in the
network.
Check if some node device in the network is replaced.
Re-configure the network.
Check if there is a change in the node address of the slave.
Check if the communication cable is disconnected or connected
loosely.
Check if the bus cable length exceeds the maximum transmission
distance. If so, the system may not be stable.
Make sure that the connection between AS01DNET-A and the
network is normal.
Check if the baud rate of AS01DNET-A is the same as that of
other node in the network.