Delta AS Series Operation Manual page 448

Hide thumbs Also See for AS Series:
Table of Contents

Advertisement

Send Quote Requests to info@automatedpt.com
Category
Error Code
H'12010111
H'12010113
H12010119
H'12010127
H'12010128
H'1201012D
H'1201012E
H'12010204
H'12010302
H'12010315
9.6.2.2 Application Error
Category
Error Code
EtherNet/
H'00010203
IP Error
Description
Adapter RPI not supported
Insufficient I/O connections
The connection of non-Listen
only is not established.
Incorrect adapter input size
Incorrect adapter output size
Consumed Tag does not
exist.
Produced Tag does not exist.
I/O connection connecting
timeout
Network bandwidth NOT
available for data
Incorrect adapter input/output
instance
Description
I/O connection timeout
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
How to fix them
3. Check the RPI for the adapter.
1. Check if the number of connections exceeds the
limit.
2. Reduce the number of the product connections.
1. Check if the system has created the I/O
connections.
2. Check the scanner I/O connection status.
Check the module number and the product setup
file to see if they match.
Check the output size in the connection
parameters.
Check if the parameters in the Consumed tag are
set correctly.
Check if the parameters in the Produced tag are
set correctly.
No response from the adapter; check if the power
and the network connection for the adapter are
working properly.
1. Check the I/O connection limit between the
scanner and the adapter.
2. Increase the RPI value or reduce the number of
connections.
Check the module number and the product setup
file to see if they match.
How to fix them
1. Check the network connection status.
2. Check if the module is working properly.
3. Increase the RPI value.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents