(4) Make sure that the summary in the CARD Utility wizard is consistent with the data restoration you want
to perform and then click Execute.
If you click Cancel in the process of restoring data to the AS Series CPU module, the data is not
completely restored. The AS Series CPU module still performs the data restoration even if you click
Cancel in the process of restoring a backup file in the memory card. You can turn off the AS Series CPU
module to stop the data restoration from being performed. To prevent the AS Series CPU module from
operating incorrectly, restore the AS Series CPU module to the factory setting, or perform the data
restoration again.
The restoration source or restoration destination may contain a password and an ID. The following table
describes the password and the ID process.
Data restoration
Memory card
 PU module
Computer
ISPSoft project
(5) After you perform the data restoration, click Home or Close in the CARD Utility wizard.
a. The ID in the backup file must be the same as the ID in the CPU module;
otherwise the data is not restored.
b. If there is a PLC password in the CPU module, the password in the backup
file must be the same as the PLC password in the CPU module. Otherwise
the data is not restored.
c. If there is no PLC password in the CPU module, and there is a password in
the backup file, the system restores the data, and the password in the backup
file becomes the PLC password in the CPU.
The ID and the password in the backup file become the program ID and the
project password in the ISPSoft project.