Delta AS Series Operation Manual page 113

Hide thumbs Also See for AS Series:
Table of Contents

Advertisement

Send Quote Requests to info@automatedpt.com
AS01DNET-A
Number
Name
1
Model name
2
State LED indicator
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Unit: mm
Description
Model name of the module
Master/slave mode:
 NS LED
OFF: no power or duplicate ID check has not been
completed.
Green light blinking every 0.5 seconds: the connection
to the DeviceNet network failed.
Green light ON: online; the connection to the DeviceNet
network is normal.
Red light blinking every 0.5 seconds: communication
error
Red light ON: Network trouble, duplicate node ID, no
network power or Bus-OFF.
 MS LED
OFF: no power
Green light blinking every 0.5 seconds: no module is
configured.
Green light ON: input and output data are normal.
Red light blinking every 0.5 seconds: when AS01DNET
works as the master, the slave in Scan List can not work
normally. When AS01DNET works as the slave, an error
occurs in the configuration.
Red light ON: hardware error
 Combination of NS LED and MS LED
NS LED OFF & MS LED OFF: no power
NS LED OFF & MS LED green light ON: duplicate ID
check has not been completed.
NS LED red light ON & MS LED green light ON: duplicate
ID check failed or Bus-OFF.
NS LED red light ON & MS LED red light blinking every
0.5 seconds: no network power
NS LED red light ON & MS LED red light ON: hardware
error

Hide quick links: