9.7.1.4 Download
The next step is to download the project to the PLC and go online.
In Studio 5000, on the Communications menu, click Who Active. To establish a connection, select the Scanner
1.
connected to the PC, and then on the Communications menu click Download.
After the connection is successfully established, the I/O status shows green by I/O OK.
2.
9.7.1.5 Data Exchange
In the Controller Organizer, you can map data, including Configuration, Input and Output parameters. When you create a
device I/O Configuration, the tags are added automatically.
Click Program Tags to display the Tags window.
1.
Tags are listed in the Name column. Tag names begin with a product name and end with C or I1 or O1, separated
2.
from the name by a colon (:).
3.
Tag name:C indicates the tag contains information from the Adapter EDS file, including Input and Output
parameters (refer to section 9.7.1.3). You can edit these parameters in the example software.
4.
Tag name:I1 indicates that the exchange starts from Tag:I1[0], and is mapped to the first parameters of the
Adapter output. The length is the output length provided by the Adapter.
5.
Tag name: O1, indicates that the exchange starts from Tag:O1[0], and is mapped to the first parameters of the
Adapter Input. The length is the input length provided by the Adapter.