Error
Code
(16#)
not used properly.
The operands HCXXX used in
0E05
DCNT are not used properly.
1000
-
System error
10FF
1300
Errors occurred in the remote
-
modules
130F
The arrangement of the I/O
1402
modules is not consistent with the
settings.
The number of connected
140B
communication modules exceed the
maximum number 4.
The number of connected
positioning modules exceed the
140C
maximum number 8.
The number of connected extension
modules exceed the maximum
140D
number 32.
More than eight remote modules on
140E
the right side of the CPU module.
The extension module ID exceeds
1600
the range.
The extension module ID cannot be
1601
set.
The extension module ID is
1602
duplicated.
The extension module cannot be
1603
operated.
Extension module communication
1604
timeout
1605
Hardware failure
Errors on the communication
1606
module function card
1607
The external voltage is abnormal.
Description
If the problem persists, contact the local authorized
distributors.
Refer to Section 12.3.7 for more information on the error
codes for the remote modules.
Check whether the settings in HWCONFIG are
consistent with the arrangement of the I/O modules.
Check the total number of communication modules.
Check the total number of positioning modules.
Check the total number of extension modules.
Check the total number of remote modules on the right
side of the CPU module (maximum is 8).
1. Make sure the module is properly connected to the
2. If the problem persists, contact the local authorized
1. Make sure the module is properly connected to the
2. If the problem persists, contact the local authorized
1. Make sure the module is properly connected to the
2. If the problem persists, contact the local authorized
1. Make sure the module is properly connected to the
2. If the problem persists, contact the local authorized
1. Make sure the module is properly connected to the
2. If the problem persists, contact the local authorized
If the problem persists, contact the local authorized
distributors.
Make sure the function card is properly connected to the
CPU module and turn the modules on again.
Check whether the external 24 V power supply to the
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Solution
CPU module and turn the modules on again.
distributors.
CPU module and turn the modules on again.
distributors.
CPU module and turn the modules on again.
distributors.
CPU module and turn the modules on again.
distributors.
CPU module and turn the modules on again.
distributors.