Classification
Temperature
measurement
Load cell
Model Name
AS02ADH-A
AS04RTD-A
AS06RTD-A
module
AS04TC-A
AS08TC-A
AS02LC-A
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Description
2-channel analog output
Hardware resolution: 12 bits
-10 to +10V, 0–20mA, 4–20mA
Conversion time: 2 ms/channel
2-channel analog input
Hardware resolution: 16 bits
0–10V, 0/1–5V, -5 to +5V, -10 to +10V, 0/4–20mA, -20 to
+20mA
High-speed conversion time: 20 µs
The analog channels are isolated from one another.
Digital output value (2000 per channel), peak value
Low-pass and band-pass filters are available.
4-channel, 2-wire/3-wire RTD
Sensor type: Pt100 / Ni100 / Pt1000 / Ni1000 / JPt100 / LG-
Ni1000 / Cu50 / Cu100 / 0-300Ω / 0-3000Ω / Ni120 (FW
V1.06 or later) input impedance
Resolution: 0.1°C/0.1°F (16 bits)
Conversion time: 200ms/channel
6-channel, 2-wire/3-wire RTD
Sensor type: Pt100 / Ni100 / Pt1000 / Ni1000 / JPt100 / LG-
Ni1000 / Cu50 / Cu100 / 0-300Ω / 0-3000Ω / Ni120 (FW
V1.06 or later) input impedance, Resolution: 0.1°C/0.1°F
(16 bits)
Conversion time: 200ms/channel
4-channel thermocouple
Sensor type: J, K, R, S, T, E, N, B and -100 to +100 mV
Resolution: 0.1°C/0.1°F (24 bits)
Conversion time: 200ms/channel
8-channel thermocouple
Sensor type: J, K, R, S, T, E, N, B and -100 to +100 mV
Resolution: 0.1°C/0.1°F (24 bits)
Conversion time: 200ms/channel
2-channel, 4-wire/6-wire load cell sensor