Power
Switch
Power
Supply
IO Module
status
CPU Module
status
 When the power is switched from OFF to ON, the power supply will be unsteady for a short time. During this
short period of time, the CPU module and I/O module are not ready to operate normally.
 When the supply power for the CPU module and the I/O module is stable, the system starts to initialize for
about 1 second. After that the I/O module is ready to be detected by the CPU module.
 The CPU module starts to wait for the set delay time to pass. Once the delay time is up, it starts to detect the
connected I/O modules locally and remotely.
It is suggested using  +  to set the delay time. Default delay time is 2 seconds.
Non-Retain Symbol Initial Value Take Effect When Stop  RUN
This determines whether the states and values of the non-latched devices are restored to initial values when the
PLC changes from Stop to Run.
 Disable: All the states and values in the non-latched devices stay the same.
 Enable: All the states and values in the non-latched devices are restored to initial values when the PLC
changes from Stop to Run. .
Retain Symbol Initial Value Take Effect When Stop  RUN
This determines whether the states and values of the latched devices are restored to initial values when the PLC
changes from Stop to Run.
 Disable: All the states and values in the latched devices stay the same.
 Enable: All the states and values in the latched devices are restored to initial values when the PLC changes
from Stop to Run. .
Assign X Input Point Control Run/Stop
This assigns an input point to have the CPU module run or stop.
 Disable: Run or stop the CPU module by the dip switch of the CPU module.
On
Off
0Vdc
Send Quote Requests to info@automatedpt.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
Call +1(800)985-6929 To Order or Order Online At Deltaacdrives.com
24Vdc
Setup
Ready
Start to detect IO
Setup
Time

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents