Download Print this page

Panasonic FP-XH Series User Manual page 81

Programmable controller
Hide thumbs Also See for FP-XH Series:

Advertisement

Configurator PMX setting items
Parameter name
Positioning repeat count
Configurator PMX settings
● When selecting "255: Repeat infinitely" in the parameter of positioning repeat count, create a
program to stop the operation using the deceleration stop function.
5.5.2 Settings and Operations of Repeat Operation
● The parameter for the repeat count is specified in the positioning parameter setting menus of
Configurator PMX.
● When the positioning table start instruction (F380 POSST) or positioning simultaneous start
instruction (F383 MPOST) is executed, the pulse output will start.
● After starting the instruction, the unit executes the pulse output for a specified repeat count
and then stops the operation. For setting to execute the operation infinitely, use this function
in combination with the deceleration stop function.
WUME-FPXHPOSG-01
Unit
Default
times
0
Settings
0 or 1
Not repeat an operation.
Repeat an operation for a specified
2 to 254
number of times.
255
Repeat an operation infinitely.
5.5 Repeat Operation
5-29

Advertisement

loading