1.2 Restrictions on Combinations and Functions
1.2.1 Applicable Versions of Unit and Software
For using the FP-XH, the software of the following versions is necessary.
Item
Programming tool
software Control FPWIN
GR / GR7 / Pro7
Configurator PMX
(Note 1)
The latest version is provided free of charge at our download center (https://
industrial.panasonic.com/ac/e/dl_center/software/). Use the latest version.
(Note 2)
To use the FP-XH in FPWIN Pro7, it is also necessary to install a setup file. For details, see the above
website.
1.2.2 Restrictions on the Combination of Pulse I/O Cassettes
There are following restrictions depending on units and cassettes to be used.
Unit Types
Relay output type
Transistor output type
1.2.3 Restrictions on I/O Allocation
● I/O signals used for each function are set in the tool software. They are allocated
automatically when set by Configurator PMX.
● Allocate the I/O numbers used for the pulse output function, high-speed counter function and
PWM output function so that they do not overlap.
■
Examples of unusable combinations
Examp
When allocating input X4 to the home input of CH0 for the pulse output function, they cannot be used
le 1
as the count input of high-speed counter CH4.
Examp
When using the output Y0 as CH0 for the pulse output function, the PWM output CH0 cannot be used.
le 2
WUME-FPXHPOSG-01
1.2 Restrictions on Combinations and Functions
Applicable version
C14/C30/C60
It is used for using the pulse output function in the table setting mode. It is
implemented in FPWIN GR / GR7 / Pro7 and activated from the option
menu.
C14R
C30R/C60R
C14T
C30T/C60T
FPWIN GR Ver.2.93 or later
FPWIN GR7 Ver.2.5 or later
FPWIN Pro7 Ver.7.03 or later
Installable
number of
cassettes
Max. 1 unit
Max. 2 units
Max. 1 unit
Max. 2 units
Pulse I/O cassette
AFPX-PLS
Installable
Uninstallable