4.
Press the [OK] button.
The screen returns to the ladder edit screen. The settings will be downloaded to the PLC
together with programs and comments.
System register relating to high-speed counter output
Classification
Pulse I/O cassette
setting
(HSC / PLS)
Control Unit input
settings
(HSC)
WUME-FPXHPOSG-01
No. and setting item
CH8
400
High-speed
counter setting
(X100 to X102)
CH9
401
CHA
High-speed
counter setting
(X200 to X202)
CHB
CH0
402
CH1
High-speed
counter
CH2
(X0 to X7)
CH3
10.2 System Register Settings
Settings
Select either Addition input (X100), Subtraction input
(X100), 2-phase input (X100, X101), Individual input
(X100, X101), or Direction distinction input (X100,
X101). You can also select a combination with Reset
input (X102).
Select either Addition input (X101) or Subtraction
input (X101). You can also select a combination with
Reset input (X102).
Select either Addition input (X200), Subtraction input
(X200), 2-phase input (X200, X201), Individual input
(X200, X201), or Direction distinction input (X200,
X201). You can also select a combination with Reset
input (X202).
Select either Addition input (X201) or Subtraction
input (X201). You can also select a combination with
Reset input (X102).
Select either Addition input (X0), Subtraction input
(X0), or 2-phase input (X0, X1).
Select either Addition input (X1) or Subtraction input
(X1).
Select either Addition input (X2), Subtraction input
(X2), or 2-phase input (X2, X3).
Select either Addition input (X3) or Subtraction input
(X3).
10-9