Download Print this page

Panasonic FP-XH Series User Manual page 143

Programmable controller
Hide thumbs Also See for FP-XH Series:

Advertisement

Counting range of elapsed value (current value) area
Section
High-speed counter
control
10.1.3 Areas Used For High-speed Counter Function
The usable combinations vary according to the unit type.
List of used areas
Transistor output
type
Channel
Input no.
No.
Single-
phase
CH0
X0
CH1
X1
CH2
X2
CH3
X3
CH4
X4
CH5
X5
CH6
X6
WUME-FPXHPOSG-01
10.1 Overview of High-speed Counter Function
Range
K–2,147,483,648 to K2,147,483,647
Relay output type
Input no.
2-phase Single-
2-phase
phase
X0, X1
X0
X0, X1
-
X1
X2, X3
X2
X2, X3
-
X3
X4, X5
X4
X4, X5
-
X5
X6, X7
X6
X6, X7
Installation
position
Control Unit
input
Control Unit
-
input
Control Unit
input
Control Unit
-
input
Control Unit
input
Control Unit
-
input
Control Unit
input
Control
Elapsed
active
value
flag
area
DT90300
R9110
DT90301
DT90304
R9111
DT90305
DT90308
R9112
DT90309
DT90312
R9113
DT90313
DT90316
R9114
DT90317
DT90320
R9115
DT90321
DT90324
R9116
DT90325
Target value
area
DT90302
DT90303
DT90306
DT90307
DT90310
DT90311
DT90314
DT90315
DT90318
DT90319
DT90322
DT90323
DT90326
DT90327
10-3

Advertisement

loading