Arrangement and Function of Control Circuit Terminal Block

The table below shows the arrangement of the control circuit terminal block, and description and spec-
ifications of each terminal.
Control Circuit Terminal Block
ROA ROB ROC
2-12
Terminal name
DC reactor connection terminal
Braking resistor connection termi-
nal
Regenerative braking unit con-
nection terminal
Control power supply auxiliary in-
put
Ground terminal
AI2
PTC
+10
AI1
AO
DO1
DO2 DOC
SP
SN
PIA
PIB
Description
Remove the short-circuit bar between the terminals
P1 and P(+), and connect an optional DC reactor.
Connect an optional braking resistor (if a braking
torque is required).
Connect optional regenerative braking units (if a
braking torque is required and that produced by the
built-in braking circuit is insufficient).
To hold a batch alarm signal when the protection
function is activated even if the main power supply
of the inverter is cut off or to display the Digital Op-
erator at all times, connect these terminals to the
power supply (at a capacity of 1.85 kW or more, for
details, refer to 2-3-4 Wiring for Main Circuit Termi-
nals on page 2-15).
This is the ground terminal. Connect this terminal to
the ground.
200-V class should be connected under type-D
grounding conditions; 400-V class should be con-
nected under type-C grounding conditions.
AIC
DI1
DI2
DI3
DI4
DI6
DI7
DIC
+24
PIZ
DIC
+24
M1 Series Standard Type User's Manual (I669)
DI5
SF1
SF2