Siemens siprotec 7SA6 User Manual page 395

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

6.14.2 Applying the Function Parameter Settings
7SA6 Manual
C53000-G1176-C133-1
The resulting single–phase AC voltage is fed to the two threshold stages 8 and
8 (see Figure 6-109). Combined with the associated time delays 7 8 and 7
8 these stages form a two-stage undervoltage protection for the positive
sequence system.
Current can be used as an additional criterion for the undervoltage protection of the
positive sequence system (current supervision &855683). An undervoltage is only
detected if the current flow is detected in at least one phase together with the
undervoltage criterion.
The undervoltage protection for the positive sequence system can be blocked via the
binary input "!8  %/.". The stages of the undervoltage protection are
automatically blocked if voltage failure is detected ("Fuse–Failure–Monitor", also see
Section 6.19.1.3) or, if the trip of the mcb for the voltage transformer is indicated via
the binary input "!)$,/)HHGHU 97" (internal blocking).
8VSSTVQV 1
"&&'
PI
„1"
PAA
I–REST> L1
I–REST> L2
I–REST> L3
U
U
L1-E
Ph–E
U
L2-E
U
U
1
L3-E
FNo 10208
>U1<(<) BLK
Figure 6-109 Logic diagram of the undervoltage protection for positive sequence voltage
system
During single-pole dead time for automatic reclosure (using the internal automatic
reclosure function) the stages of the undervoltage protection are automatically
blocked in the positive sequence system so that they do not respond to the reduced
voltage cause by the disconnected phase in case the voltage transformers are located
on the outgoing side.
The voltage protection can only operate if it has been set to (QDEOHG during the
configuration of the device scope (see Section 5.1, address ).
The overvoltage and undervoltage stages can detect phase–to–earth voltages,
phase–to–phase voltages or the symmetrical positive sequence system of the
≥1
"&&! V 1
&
U<
UÃV 1
UÃV 11
&
U<<
"&&# V 11
Functions
FNo 10300
U1< Pickup
FNo 10302
T
0
T U1< TimeOut
"&&"
FNo 10304
≥1
U1<(<) TRIP
"&&$
FNo 10303
T
0
T U1<< TimeOut
FNo 10301
U1<< Pickup
6-213