Siemens siprotec 7SA6 User Manual page 570

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

Installation and Commissioning
8-26
Table 8-13
Jumper setting of relay contact for BO6.
Jumper
Quiescent state open
(NO contact)
X41
1–2
The set nominal currents of the current input transformers are checked on the input/
output board C–I/O–2. All jumpers must be set to the same nominal current, i.e. one
jumper for each input transformer (X61 to X64) and one common jumper X60.
However: There is no jumper X64 for the version with sensitive earth current input
(input transformer T8).
The jumpers X71, X72 and X73 on the input/output board C–I/O–2 are for setting the
bus address and must not be changed. Table 8-14 lists the jumper presettings.
Mounting location:
1
ê in Figure 8-8, slot 19,
for housing size
/
3
1
ê in Figure 8-9, slot 33,
for housing size
/
2
1
ê in Figure 8-10, slot 33 right.
for housing size
/
1
Table 8-14
Jumper setting of printed circuit board addresses of binary input/output
boards C-I/O-2
Jumper
Presetting
X71
1–2 (H)
X72
1–2 (H)
X73
2–3 (L)
Quiescent state closed
(NC contact)
2–3
C53000-G1176-C133-1
Presetting
1–2
7SA6 Manual