Siemens siprotec 7SA6 User Manual page 741

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

Addr.
Setting Title
3477
3.AR Tdead 3Flt
3478
3.AR Tdead1Trip
3479
3.AR Tdead3Trip
3480
3.AR: Tdead EV.
3481
3.AR: CB? CLOSE
3482
3.AR SynRequest
3483
4.AR: START
3484
4.AR: T-ACTION
3486
4.AR Tdead 1Flt
3487
4.AR Tdead 2Flt
3488
4.AR Tdead 3Flt
3489
4.AR Tdead1Trip
3490
4.AR Tdead3Trip
3491
4.AR: Tdead EV.
3492
4.AR: CB? CLOSE
3493
4.AR SynRequest
3501
FCT Synchronism
3502
Dead Volt. Thr.
3503
Live Volt. Thr.
3504
Umax
3507
T-SYN. DURATION Synchronism and
3508
T SYNC-STAB
3510
Op.mode with AR
3511
Max. Volt. Diff
3512
Max. Freq. Diff
3513
Max. Angle Diff
3515A
SYNC-CHECK
7SA6 Manual
C53000-G1176-C133-1
Function
Setting Options
0.01..1800.00 sec; ∞
Automatic Reclo-
sure
0.01..1800.00 sec; ∞
Automatic Reclo-
sure
0.01..1800.00 sec; ∞
Automatic Reclo-
sure
Automatic Reclo-
0.01..1800.00 sec
sure
Automatic Reclo-
YES
sure
NO
Automatic Reclo-
YES
sure
NO
Automatic Reclo-
YES
sure
NO
0.01..300.00 sec; ∞
Automatic Reclo-
sure
0.01..1800.00 sec; ∞
Automatic Reclo-
sure
0.01..1800.00 sec; ∞
Automatic Reclo-
sure
0.01..1800.00 sec; ∞
Automatic Reclo-
sure
0.01..1800.00 sec; ∞
Automatic Reclo-
sure
0.01..1800.00 sec; ∞
Automatic Reclo-
sure
Automatic Reclo-
0.01..1800.00 sec
sure
Automatic Reclo-
YES
sure
NO
Automatic Reclo-
YES
sure
NO
Synchronism and
ON
Voltage Check
OFF
Synchronism and
1..60 V
Voltage Check
Synchronism and
20..125 V
Voltage Check
Synchronism and
20..140 V
Voltage Check
0.01..600.00 sec; ∞
Voltage Check
Synchronism and
0.00..30.00 sec
Voltage Check
Synchronism and
with consideration of CB
Voltage Check
closing time
without consideration of CB
closing time
Synchronism and
1.0..40.0 V
Voltage Check
Synchronism and
0.03..2.00 Hz
Voltage Check
2..60 °
Synchronism and
Voltage Check
Synchronism and
YES
Voltage Check
NO
Default Setting
0.50 sec
Dead time after 3phase faults
∞ sec
Dead time after 1pole trip
0.50 sec
Dead time after 3pole trip
1.20 sec
Dead time after evolving fault
NO
CB ready interrogation before reclos-
ing
NO
Request for synchro-check after 3pole
AR
NO
AR start allowed in this cycle
0.20 sec
Action time
1.20 sec
Dead time after 1phase faults
1.20 sec
Dead time after 2phase faults
0.50 sec
Dead time after 3phase faults
∞ sec
Dead time after 1pole trip
0.50 sec
Dead time after 3pole trip
1.20 sec
Dead time after evolving fault
NO
CB ready interrogation before reclos-
ing
NO
Request for synchro-check after 3pole
AR
ON
Synchronism and Voltage Check func-
tion
5 V
Voltage threshold dead line / bus (ph-
e)
90 V
Voltage threshold live line / bus (ph-e)
110 V
Maximum permissible voltage
1.00 sec
Maximum duration of synchronism-
check
0.00 sec
Synchronous condition stability timer
without consideration of CB
Operating mode with AR
closing time
2.0 V
Maximum voltage difference
0.10 Hz
Maximum frequency difference
10 °
Maximum angle difference
YES
Live bus / live line and Sync before AR
Appendix
Comments
B-17