Applying The Function Parameter Settings; Settings - Siemens siprotec 7SA6 User Manual

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

6.20.6 Applying the Function Parameter Settings

6.20.7 Settings

Fault display
Addr.
Setting Title
610
FltDisp.LED/LCD
615
Spont. FltDisp.
7SA6 Manual
C53000-G1176-C133-1
TRIP
CLOSE
UHvÃUSDQÃ8€q
!#
Figure 6-147 Trip/Close test cycle
The configuration concerning the tripping logic of the device as a whole and circuit-
breaker test function was already set in accordance with the general data in
Subsection 6.1.3 and 6.1.1.
Furthermore, the setting in address  )OW'LVS/('/&', determines whether
the fault messages which are allocated to the local LEDs as well as the spontaneous
messages that are displayed via the LCD on the front of the device following a fault,
are stored following each fault detection of a protection function ( with PICKUP ), or if
storage only takes place if a trip command is issued ( with TRIP = "No trip no flag"-
feature).
Setting Options
Display Targets on every
Pickup
Display Targets on TRIP only
NO
YES
U87‡r†‡qrhq
UHh‘Ã8GPT@Ã8H9
!#!
Default Setting
Display Targets on
every Pickup
NO
Functions
t
!#
Comments
Fault Display on LED / LCD
Spontaneous display of flt.an-
nunciations
6-281