Siemens siprotec 7SA6 User Manual page 188

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

Functions
Primary or
Secondary Values
Additional Settings
Confirmation
Exiting the
Setting Mode
6-6
acknowledge the message, click 2., and the original value reappears. A new entry
can be made or another setting value can be modified.
Setting values can be entered and displayed in primary terms or secondary terms, as
®
desired. DIGSI
4 automatically performs the conversions based on the settings
entered for the transformer data and conversion ratios.
To switch between primary values and secondary values:
q
Click on 2SWLRQV in the menu bar, as shown in Figure 6-7.
q
Click on the desired alternative.
Another method is available by using the buttons
Figure 6-7
Selection of primary or secondary value entry — example
Those settings that are modified only in special cases are typically hidden. They may
be made visible by checking on 'LVSOD\ $GGLWLRQDO 6HWWLQJV.
Each entry may be confirmed by clicking $SSO\. Valid values are accepted
automatically when another field is selected.
The final acceptance of a modified setting takes place once the setting mode is exited
(see below "Exiting the Setting Mode").
The dialogue box may be closed by clicking 2.. Once closed, another function may
be selected for setting modification, or you can exit the setting mode.
In order to transfer the modified setting values to the relay, the user should click on
',*6, → 'HYLFH. The user will be prompted for Password No. 5. After entering the
password and confirming with 2., data is transferred to the relay where modifications
become effective.
on the toolbar.
7SA6 Manual
C53000-G1176-C133-1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents