Technical Data
Binary Outputs
10-4
Nominal voltage
Switching thresholds
– for nominal voltages 24/48 VDC
60/110/125 VDC
– for nominal voltages 110/125/
220/250 VDC
Current consumption, energized
Maximum permissible voltage
Impulse filter on input
Alarm / command relay (see also General Diagrams in Appendix A, Section A.2)
Number and Information
Order Variant
7SA610∗–∗A/E/J
7SA610∗–∗B/F/K
7SA6∗1∗–∗A/E/J
7SA6∗1∗–∗B/F/K
7SA6∗2∗–∗A/E/J
7SA6∗2∗–∗B/F/K
7SA6∗2∗–∗C/G/L
Switching capability
Switching voltage
Permissible current per contact
pulse current
Total permissible current
on common paths
Max. switching
capability for 30 s
Permissible relative closing time
Operating time, approx.
24 VDC to 250 VDC in 3 ranges, bipolar
adjustable with jumpers
U
pick-up
U
drop-off
U
pick-up
U
drop-off
approx. 1.8 mA
independent of the control voltage
300 VDC
220 nF coupling capacity at 220 V
with recovery time >60 ms
acc. to the order variant
(allocatable)
NO
Contact
(normal)
7
5
7
8
14
21
11
MAKE
BREAK
/
for 28 V to 250 V
for 24 V
8 ms
≥ 19 VDC
≤ 14 VDC
≥ 88 VDC
≤ 66 VDC
NO
NO/NC
Contact
(switch
(fast)
select-
able)
1
7
2
7
3
7
4
1000 W/VA
30 W ohmic
40 W for L/R
50 ms
25 W/VA
250 V
5 A permanent
30 A
0.5 s
5 A permanent
30 A for 0.5 s
5 ms
8 ms
C53000-G1176-C133-1
Power
Relay
4
8
250 V
30 A
0.5 s
1000 W
500 W
1 %
7SA6 Manual