Siemens siprotec 7SA6 User Manual page 431

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

Fault Location
7SA6 Manual
C53000-G1176-C133-1
for analog output 1 at mounting location "D" (Port D1):
Address   P$ '
Address  0,1 9$/8( ' the minimum value permitted
for analog output 2 at mounting location "D" (Port D2):
Address   P$ '
Address  0,1 9$/8( ' the minimum value permitted
The maximum value is 22.0 mA. If it is exceeded (value outside of the maximum
permissible range), then a value of 22.5 mA is output.
Example:
The phase current I
is output as analog output 1 at mounting location "B". The
L2
operational nominal current should correspond to 10 mA output, which means that
20 mA correspond to a rate of 200 %. Values below 4 mA are not valid.
Settings:
Address   P$ %
Address  0,1 9$/8( % =  mA.
For the fault location the conversion factor, i. e. the value to be output, is also set to
20 mA. Dependening on whether the fault location should be output in per cent of the
line length or in length unit, set the following:
For analog output 1 at mounting location "B" (Port B1):
Address   P$ %
or
Address  or   P$ %
to be indicated at 20 mA.
For analog output 2 at mounting location "B" (Port B2):
Address   P$ %
or
Address  or   P$ %
is required to be indicated at 20 mA.
For analog output 1 at mounting location "D" (Port D1):
Address   P$ '
or
Address  or   P$ '
is required to be indicated at 20 mA.
For analog output 2 at mounting location "D" (Port D2):
Address   P$ '
20 mA
or
Address  or   P$ '
to be indicated at 20 mA.
Set in Addresses  1(* 9$/8( % ,  1(* 9$/8( % ,  1(*
9$/8( ' or  1(* 9$/8( ' which output value is to be indicated in case
the fault location is negative (fault in reverse direction). In addresses  29(5)/2:
% ,  29(5)/2: % ,  29(5)/2: ' or  29(5)/2: '
the value of the numerical overflow (fault outside the maximum permissible range) is
set.
value in % to be indicated at 20 mA
value in % to be indicated at 20 mA
 %,
value in % to be indicated at 20 mA
value in kilometres or miles that is
value in % to be indicated at 20 mA
value in kilometres or miles that
value in % to be indicated at 20 mA
value in kilometres or miles that
the value in % that is required to be indicated at
value in kilometres or miles
Functions
6-249