Configuration
Table 5-4
Selection guide for function modules and
Function Modules
ABSVALUE
Magnitude calculation
AND
AND-gate
BOOL_TO_CO
Boolean to control, conversion
BOOL_TO_DI
Boolean to double point,
conversion
BOOL_TO_IC
Boolean to internal single
point, conversion
BUILD_DI
Create double point
annunciation
CMD_INF
Test
5-38
Figure 5-34
Establishing the
Within the Run Sequence menu, select (GLW, and then 3UHGHFHVVRU IRU
,QVWDOODWLRQ, to ensure that the function modules selected from the library will be
implemented into the desired task level (Figure 5-35).
Figure 5-35
Assignment of function modules to the selected
The proper assignment is important for several reasons. For example, if interlocking
logic were to be set up in the measured values task level, indications would constantly
be created by the cyclical processing, filling the buffer unnecessarily. On the other
hand, the interlocking condition at the moment of a switching operation may not be
processed at the right time, since measured value processing is done cyclically every
600 ms.
Description
task level
task level
s
Run-Time Level
MW_BEARB
PLC1_BEARB
Meter processing
Slow PLC
X
X
X
X
X
X
task level
PLC_BEARB
SFS_BEARB
Fast PLC
Interlocking
X
X
X
X
X
X
X
X
X
X
7SA6 Manual
C53000-G1176-C133-1