Siemens siprotec 7SA6 User Manual page 734

Distance protection
Hide thumbs Also See for siprotec 7SA6:
Table of Contents

Advertisement

Appendix
Addr.
Setting Title
2109A
TrBlk Wait Time
2110A
TrBlk BlockTime
2201
FCT Direct Trip
2202
Trip Time DELAY
2401
FCT SOTF-O/C
2404
I>>>
2501
FCT Weak Infeed
2502A
Trip/Echo DELAY
2503A
Trip EXTENSION
2505
UNDERVOLTAGE
2601
Operating Mode
2610
Iph>>
2611
T Iph>>
2612
3I0>> PICKUP
2613
T 3I0>>
2614
I>> Telep/BI
2615
I>> SOTF
2620
Iph>
2621
T Iph>
2622
3I0>
2623
T 3I0>
2624
I> Telep/BI
2625
I> SOTF
2630
Iph> STUB
2631
T Iph STUB
2632
3I0> STUB
2633
T 3I0 STUB
2634
I-STUB Telep/BI
2635
I-STUB SOTF
2640
Ip>
2642
T Ip Time Dial
2643
Time Dial TD Ip
B-10
Function
Setting Options
0.00..30.00 sec; ∞
Teleprotection for
Distance prot.
Teleprotection for
0.00..30.00 sec
Distance prot.
DTT Direct Trans-
ON
fer Trip
OFF
0.00..30.00 sec; ∞
DTT Direct Trans-
fer Trip
Instantaneous High-
ON
Speed SOTF Over-
OFF
current
Instantaneous High-
1.00..25.00 A
Speed SOTF Over-
current
Weak Infeed (Trip
OFF
and/or Echo)
Echo only
Echo and Trip
Weak Infeed (Trip
0.00..30.00 sec
and/or Echo)
Weak Infeed (Trip
0.00..30.00 sec
and/or Echo)
Weak Infeed (Trip
2..70 V
and/or Echo)
Backup overcurrent ON
Only Active with Loss of VT
sec. circuit
OFF
Backup overcurrent 0.10..25.00 A; ∞
Backup overcurrent 0.00..30.00 sec; ∞
Backup overcurrent 0.05..25.00 A; ∞
Backup overcurrent 0.00..30.00 sec; ∞
Backup overcurrent NO
YES
Backup overcurrent NO
YES
Backup overcurrent 0.10..25.00 A; ∞
Backup overcurrent 0.00..30.00 sec; ∞
Backup overcurrent 0.05..25.00 A; ∞
Backup overcurrent 0.00..30.00 sec; ∞
Backup overcurrent NO
YES
Backup overcurrent NO
YES
Backup overcurrent 0.10..25.00 A; ∞
Backup overcurrent 0.00..30.00 sec; ∞
Backup overcurrent 0.05..25.00 A; ∞
Backup overcurrent 0.00..30.00 sec; ∞
Backup overcurrent NO
YES
Backup overcurrent NO
YES
Backup overcurrent 0.10..4.00 A; ∞
Backup overcurrent 0.05..3.00 sec; ∞
Backup overcurrent 0.50..15.00; ∞
Default Setting
0.04 sec
Transient Block.: Duration external flt.
0.05 sec
Transient Block.: Blk.T. after ext. flt.
OFF
Direct Transfer Trip (DTT)
0.01 sec
Trip Time Delay
ON
Inst. High Speed SOTF-O/C is
2.50 A
I>>> Pickup
Echo only
Weak Infeed function is
0.04 sec
Trip / Echo Delay after carrier receipt
0.05 sec
Trip Extension / Echo Impulse time
25 V
Undervoltage (ph-e)
Only Active with Loss of VT
Operating mode
sec. circuit
2.00 A
Iph>> Pickup
0.30 sec
T Iph>> Time delay
0.50 A
3I0>> Pickup
2.00 sec
T 3I0>> Time delay
YES
Instantaneous trip via Teleprot./BI
NO
Instantaneous trip after SwitchOnTo-
Fault
1.50 A
Iph> Pickup
0.50 sec
T Iph> Time delay
0.20 A
3I0> Pickup
2.00 sec
T 3I0> Time delay
NO
Instantaneous trip via Teleprot./BI
NO
Instantaneous trip after SwitchOnTo-
Fault
1.50 A
Iph> STUB Pickup
0.30 sec
T Iph STUB Time delay
0.20 A
3I0> STUB Pickup
2.00 sec
T 3I0 STUB Time delay
NO
Instantaneous trip via Teleprot./BI
NO
Instantaneous trip after SwitchOnTo-
Fault
∞ A
Ip> Pickup
0.50 sec
T Ip Time Dial
5.00
Time Dial TD Ip
Comments