Jumper setting for the contact type of relay for BO9
Module
for
Jumper
Slot 19
BO9
X40
With device versions 7SA6*2–A... and 7SA6*2–B... (housing size
input/output boards C–I/O–1 (Figure 8-13, slot 19 left and right, as well as slot 33 left)
the relays for the binary outputs BO9, BO17 and BO25 (depending on the version) can
be changed from normally closed to normally open (refer to General Diagrams in
the Appendix A under Section A.2).
Table 8-8
Jumper setting for the contact type of relay for BO9, BO17 and BO25
Module
for
Jumper
Slot 33
BO 9
X40
left
Slot 19
BO17
X40
right
Slot 19
BO25
X40
left
Checking control voltages of binary inputs:
BI6 to BI13 (for housing size
BI6 to BI29 (for housing size
Table 8-9
Jumper setting of control voltages of binary inputs BI6 to BI13 on the binary in-
put/output boards C– I/O–1 for housing size
Binary inputs
Jumper
Slot 19
BI6
X21/X22
BI7
X23/X24
BI8
X25/X26
BI9
X27/X28
BI10
X29/X30
BI11
X31/X32
BI12
X33/X34
BI13
X35/X36
1
) Factory settings for devices with power supply voltages of 24 VDC to 125 VDC
2
) Factory settings for devices with power supply voltages of 110 VDC to 250 VDC and 115 VAC
Quiescent state
open (NO contact)
closed (NC contact)
1–2
Quiescent state
open (NO contact)
closed (NC contact)
1–2
1–2
1–2
1
/
) according to Table 8-9,
2
1
/
, depending on version) according to Table 8-10.
1
1
Threshold 17 V
)
L
L
L
L
L
L
L
L
Installation and Commissioning
Quiescent state
2–3
1
/
) the contact of
1
Quiescent state
2–3
2–3
2–3
1
/
2
2
Threshold 73 V
)
M
M
M
M
M
M
M
M
Presetting
1–2
Presetting
1–2
1–2
1–2
8-23