Addr.
Setting Title
138
Fault Locator
139
BREAKER FAIL-
URE
140
TripCirc.Superv
142
Ther. OVERLOAD
150
AnalogOutput B1
151
AnalogOutput B2
152
AnalogOutput D1
153
AnalogOutput D2
201
CT Starpoint
203
Unom PRIMARY
204
Unom SECOND-
ARY
205
CT PRIMARY
206
CT SECONDARY
207
SystemStarpoint
210
U4 transformer
211
Uph / Udelta
7SA6 Manual
C53000-G1176-C133-1
Function
Setting Options
Scope of Functions Disabled
Enabled
with BCD-output
Scope of Functions Disabled
Enabled
Scope of Functions Disabled
1 trip circuit
2 trip circuits
3 trip circuits
Scope of Functions Disabled
Enabled
Scope of Functions Disabled
IL2 [%]
UL23 [%]
|P| [%]
|Q| [%]
Fault location d [%]
Fault location d [km]
Trip current Imax [primary]
Scope of Functions Disabled
IL2 [%]
UL23 [%]
|P| [%]
|Q| [%]
Fault location d [%]
Fault location d [km]
Trip current Imax [primary]
Scope of Functions Disabled
IL2 [%]
UL23 [%]
|P| [%]
|Q| [%]
Fault location d [%]
Fault location d [km]
Trip current Imax [primary]
Scope of Functions Disabled
IL2 [%]
UL23 [%]
|P| [%]
|Q| [%]
Fault location d [%]
Fault location d [km]
Trip current Imax [primary]
Power System Data
towards Line
1
towards Busbar
Power System Data
1.0..1200.0 kV
1
Power System Data
80..125 V
1
Power System Data
10..5000 A
1
Power System Data
1A
1
5A
Power System Data
Solid Earthed
1
Peterson-Coil earthed
Isolated
Power System Data
not connected
1
Udelta transformer
Usync transformer
Ux reference transformer
Power System Data
0.10..9.99
1
Default Setting
Enabled
Fault Locator
Disabled
Breaker Failure Protection
Disabled
Trip Circuit Supervision
Disabled
Thermal overload protection
Disabled
Analog Output B1 (Port B)
Disabled
Analog Output B2 (Port B)
Disabled
Analog Output D1 (Port D)
Disabled
Analog Output D2 (Port D)
towards Line
CT Starpoint
400.0 kV
Rated Primary Voltage
100 V
Rated Secondary Voltage (L-L)
1000 A
CT Rated Primary Current
1A
CT Rated Secondary Current
Solid Earthed
System Starpoint is
not connected
U4 voltage transformer is
1.73
Matching ratio Phase-VT To Open-
Delta-VT